Determining optimal thermal energy storage charging temperature for cooling using integrated building and coil modeling
arxiv.org·3d
♨️Heat Pumps
Preview
Report Post

arXiv:2601.10976v1 Announce Type: new Abstract: Thermal energy storage (TES) systems coupled with heat pumps offer significant potential for improving building energy efficiency by shifting electricity demand to off-peak hours. However, conventional operating strategies maintain conservatively low chilled water temperatures throughout the cooling season, a practice that results in suboptimal heat pump performance. This study proposes a physics-based integrated simulation framework to determine the maximum feasible chilled water supply temperature while ensuring cooling stability. The framework integrates four submodels: relative humidity prediction, dynamic cooling load estimation, cooling coil performance prediction, and TES discharge temperature prediction. Validation against measured da…