Graph-ESBMC-PLC: Formal Verification of Graphical PLCopen XML Ladder Diagram Programs Using SMT-Based Model Checking (opens in new tab)
PLCopen XML defines two encoding formats for IEC 61131-3 Ladder Diagram programs: a textual encoding using elements, and a graphical encoding that represents rung logic as a directed graph of localId/refLocalId connections. ESBMC-PLC supported the textual format but parsed graphical exports from CONTROLLINO, Beremiz, and OpenPLC Editor into an empty GOTO intermediate representation, causing vacuous verification success. This paper presents Graph...